Permit #B1901495
Address2311 WILSON BLVD
TypeCTBO
StatusFINALED
Permit HolderECKO BUILDING SERVICES LLC
OwnerOTTER WILSON BOULEVARD LLC
Applied Date05/30/2019
Approved Date07/31/2019
Date Issued08/01/2019
DescriptionINTERIOR ALTERATIONS FOR A NEW COFFEE SHOP - FOR FIVE COFFEE ROASTERS. - REQUIRES HEALTH REVIEW

  View Event Log.      View Status.       View Required Plan Review       View Printer Version.   
  
  
Search Again

 
ReviewEnergy
Review Date06/12/2019
StatusApproved
Comments
Sheet M-700 includes a Water Source Heat Pump Unit Schedule. The 2012 Virginia Energy Conservation Code (VECC) Table C403.2.3(2) requires that Water Source Heat Pumps (WSHP) have a minimum COP of 4.2 or higher at 68 degrees F entering water temperature. The design indicates these WSHP units have a COP of 4.03 and 3.82.
In the resubmission revise the WSHP schedule to indicate compliance with Table C403.2.3(2 of the 2012 VECC.
  



  
 